Home
UV  and IR Flame Detector (Ex)
Reflective Beam Detector
Addressable/Intelligent  fire alarm
Conventional Fire alarm series
Promotional products
Domestic fire alarm
Addressable Fire Alarm System
Conventional Fire Alarm System
Product Catalog
Battery Powered smoke detector
Conventional Smoke Detector
Conventional Heat Detector
Conventional Fire Alarm Control Panel
Fire Fighting System
 Manual Call Point bell strobe
Gas Detector and Co Detector
4wire detector with relay output
TC Addressable fire alarm system
Infrared Alarm System
Addressable Fire Alarm System
Addressable fire alarm system
News
Contact Us
Documents

Product Catalog 

 

4 zones conventional fire alarm security host control panel CK1004

  • 4 zones conventional fire alarm security host control panel	CK1004
  • 4 zones conventional fire alarm security host control panel	CK1004
  • 4 zones conventional fire alarm security host control panel	CK1004
  • 4 zones conventional fire alarm security host control panel	CK1004
  • 4 zones conventional fire alarm security host control panel	CK1004
Model No.︰ck1004
Brand Name︰zc
Country of Origin︰China
Unit Price︰US $ 130 / pc
Minimum Order︰1 pc
Share on:

 Total 9 Related Items 
Prev56789Next

Product Description
Conventional Fire Alarm Control System :Conventional Fire Alarm Control Panel
 



 

General

Conventional Fire Alarm Control Panel with four Zones

Key Specifications/Special Features

  • Four Style B (Class B) Initiating Device Circuits (IDCs).
  • All zones accept two-wire smoke detectors and any normally-open contact devices.
  • One built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
  • Alarm, Trouble and Supervisory, Form-C relays standard.
  • 24-volt operation.
  • Resettable four-wire smoke detector power @ 500 mA.
  • Non-resettable power @ 500 mA.
  • One-man walk-test programmable for silent or audible test.
  • Disable/Enable control per IDC.
  • Reverse polarity protection.

Specifications

 

AC Power

90-270 VAC, 50 Hz, 2.3 amps

Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation

Battery (lead acid only)

Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp

Maximum Charger Capacity: 18 Amp Hour batter

Sound Output Device Circuits

General Alarm Zones 1 through 16

Operation: All zones Class B

Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)

Alarm Current: 15 mA threshold

Short Circuit Current: 42 mA maximum

Maximum Loop Resistance: 100 ohms

End-of-Line Resistor: 4.7K, ½ watt

Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone

Standby Current: 7.26 mA

Three Relays Output

Relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)

Nonresettable 24 VDC Power

Maximum ripple voltage: 10 mVRMS          Operating Voltage nominal 24 volts

Total DC current available from this output is up to 500 mA

Recommended maximum Standby current is 150 mA

 

Payment Terms︰T/T,WU,PAYPAL
Product Image






Related Products
4/8/12/16/24Zones Conventional Fire Alarm Control Panel
4/8/12/16/24Zones Conventional Fire Alarm Control Panel
US $ 105
4Zones Conventional Fire Alarm Control Panel
4Zones Conventional Fire Alarm Control Panel
US $ 110
8Zones Conventional Fire Alarm controller master panel
8Zones Conventional Fire Alarm controller master panel
US $ 120
16 Zones Conventional Fire Alarm Control Panel Controller Alarm host
16 Zones Conventional Fire Alarm Control Panel Controller Alarm host
US $ 147

Home  |  UV and IR Flame Detector (Ex)  |  Reflective Beam Detector  |  Addressable/Intelligent fire alarm  |  Conventional Fire alarm series  |  Promotional products  |  Domestic fire alarm  |  Addressable Fire Alarm System  |  Conventional Fire Alarm System  |  Product Catalog  |  News  |  Contact Us  |  Documents  |  Sitemap  |  Mobile Version
  English     简体版     繁體版
Powered by DIYTrade.com